BRL K536-A Plastics piping systems of PVC-C for hot and cold drinking water

The products are intended to be applied in piping systems for hot and cold water distribution at a design pressure (= maximum operating pressure) of 8 or 10 bar (9 or 11 bar absolute or 8 or 10 bar overpressure), under the conditions mentioned in table 1.

Tabel 1 – Temperature profile during 50 years

  Temperature
[ ºC]
Lifetime Overall service coefficient
Toperation 70 49 years 1,8
Tmax 80 1 years 1,7
T malfunction 95 100 hours 1,0
Remark: the mentioned
temperature profile is in
accordance with class 2
of ISO 10508
     

For who?

Installers/plumbers, architects, contractors, municipalities, housing association.